Goodrive300-01 inverter for air compressor                                                                Function parameters 
-72- 
Detailed instruction of parameters 
Braking retention 
time before   
starting   
circuit braking.   
When the running frequency is lower than P01.09 
during the stopping of the inverter, set 13.15 to a 
non-zero value to enter into stopping short circuited 
braking and then carry out the DC braking at the time 
set by P01.12 (refer to the instruction of 
P01.09~P01.12) . 
Setting range of P13.13: 0.0~150.0% (inverter) 
Setting range of P13.14: 0.00~50.00s 
Setting range of P13.15: 0.00~50.00s 
The braking 
retention time 
when stopping     
P14 Group    Serial communication 
Local 
communication 
address 
The setting range: 1~247   
When the master is writing the frame, the 
communication address of the slave is set to 0; the 
address is the communication address. All slaves on 
the MODBUS bus can receive the frame, but the 
salve does not respond. 
The communication of the drive is unique in the 
communication net. This is the fundamental for the 
point to point communication between the upper 
computer and the inverter.   
Note: The address of the slave cannot set to 0. 
Set  the  digital  transmission  speed  between  the 
upper computer and the inverter. 
0: 1200BPS 
1: 2400BPS 
2: 4800BPS 
3: 9600BPS 
4: 19200BPS 
5: 38400BPS 
6: 57600BPS 
7: 115200BPS 
Note: The baud rate between the upper computer 
and  the  inverter  must  be  the  same.  Otherwise, 
the communication is not applied. The bigger the 
baud rate, the quicker the communication speed. 
The data format between the upper computer and 
the inverter must be the same. Otherwise, the 
communication is not applied.