Goodrive300-01 inverter for air compressor Function parameters
-74-
Detailed instruction of parameters
LED tens:
0: Communication encrypting invalid
1: Communication encrypting valid
P17 Group Monitoring function
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
Display current ramp reference frequency of the
inverter
Range: 0.00Hz~P00.03
Display current output voltage of the inverter
Range: 0~1200V
Display current output current of the inverter
Range: 0.0~3000.0A
Display the rotation speed of the motor
Range: 0~65535RPM
Display current torque current of the inverter
Range: 0.0~3000.0A
Display current exciting current of the inverter
Range: 0.0~3000.0A
Display current power of the motor. 100.0%
corresponds to the rated power of the motor. The
positive value is in electromotion state while the
negative value is in power generating state.
Setting range: -300.0%~300.0% (motor rated power)
Display the current output torque of the inverter.
100.0% corresponds to the rated torque of the
motor. During FWD rotation, the positive value is in
electromotion state while the negative value is in
power generating state. During REV rotation, the
states are on the contrary.
Range: -250.0~250.0%
Evaluated motor
frequency
Evaluate the motor rotor frequency on open loop
vector
Range: 0.00~ P00.03
Display current DC bus voltage of the inverter
Range: 0.0~2000.0V