Goodrive300-01 inverter for air compressor Function parameters
-79-
Detailed instruction of parameters
Counting period of
PID temperature
(Ts)
Convergence
coefficient (K)
PID temperature
upper limit
PID temperature
lower limit
Pt100 temperature
compensation
compensation
coefficient of
Pt100 temperature
Upper-limit
frequency
decreasing
pressure
0.00~ P18.04
When the current pressure is larger than the value,
the upper-limit frequency will decrease.
Upper-limit
frequency
decreasing ratio
0.00Hz~10.00Hz
When the current pressure is larger than P18.30,
increase 0.01Mpa, corresponding upper-limit
frequency reduction.
P19 Group State group for air compressor
Set time for
maintenance of
component 1
0~65535h
Pre-alarm when the accumulated service time of
component 1 exceeds the set value; pre-alarm is
invalid when the set value=0.
Set time for
maintenance of
component 2
0~65535h
Pre-alarm when the accumulated service time of
component 2 exceeds the set value; pre-alarm is
invalid when the set value=0.
Set time for
maintenance of
component 3
0~65535h
Pre-alarm when the accumulated service time of
component 3 exceeds the set value; pre-alarm is
invalid when the set value=0.