Goodrive300-LIFT series inverter    Commissioning guidelines 
-80- 
Note: 
•  Set the motor parameters according to the motor name plate. 
•  Note the difference in synchronous and asynchronous motor parameter autotuning modes. 
7.4.2 Adjusting maintenance running parameters 
Maintenance running can be used to check whether the lift is running properly. 
During maintenance, check whether the actual lift running direction is the same as the direction in the 
command. If not, exchange any two cables of U, V, and W or set P00.06=1. 
Note:  For  the  synchronous  motor,  changing  the  motor  cables  requires  autotuning  the  motor 
parameter (pole angle) again. It is recommended to set P00.06 to change the lift running direction. 
7.4.3 Adjusting the S curve for normal running 
Before normal running, check whether the control logic is correct and wiring is correct. If they are 
correct, adjust the S curve. For details, see the descriptions of P09.09–P09.16. 
Starting  frequency  of  direct 
startup 
Starting  frequency  retention 
time 
Stop knee-point frequency 
S-curve  ACC  start  segment 
duration 
S-curve  ACC  end  segment 
duration 
S-curve  DEC  start  segment 
duration 
S-curve  DEC  end  segment 
duration 
S-curve  start  segment  duration 
during stop 
S-curve  end  segment  duration 
during stop 
DEC time for creeping to stop