EasyManua.ls Logo

INVT GD350-2R2G-4 - Page 133

INVT GD350-2R2G-4
341 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350 series high-performance multi-function inverter Chapter 6
-128-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
RunSleep
t1 t2
Run
Time t
Output frequency f
t3=P01.20
t1t2, the inverter does not run
t1+t2=t3, the inverter runs
t3
Setting range: 0.03600.0s (valid when P.01.19 is 2)
P01.21
Restart after
power cut
This function code sets the automatic running of the
inverter at next power-on after power down.
0: Disabled restart
1: Enable restart, namely the inverter will run
automatically after the time set by P01.22 elapses if
the starting conditions are met.
0
P01.22
Waiting time of
restart after
power cut
This function code sets the waiting time before
automatically running at next power-on after power
down.
Output frequency
Running
Power off
Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.03600.0s (valid when P01.21 is 1)
1.0s
P01.23
Start delay
This function code sets the delay of the inverters
wake-up-from-sleep after running command is given,
the inverter will start to run and output after the time
set by P01.23 elapses to realize brake release.
Setting range: 0.0600.0s
0.0s
P01.24
Stop speed delay
0.0600.0s
0.0s
P01.25
Open-loop 0Hz
output selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
P01.26
Deceleration time
of
emergency-stop
0.060.0s
2.0s
P01.27
Time of starting
section of
deceleration S
curve
0.050.0s
0.1s

Table of Contents

Related product manuals