Goodrive350 series high-performance multi-function inverter Appendix D
-317-
Inverter model
Recommended
cable size
(mm
2
)
Size of connectable cable (mm
2
)
Terminal
screw
specification
Tightening
torque
(Nm)
RST
UVW
PE
RST
UVW
P1, (+)
PB, (+),
(-)
PE
GD350-160G-6
95
50
95150
95150
25150
50150
Nuts are used as
terminals, so it is
recommended that you
use a wrench or sleeve.
GD350-185G-6
95
50
95150
95150
25150
50150
GD350-200G-6
120
70
120300
120300
35300
70240
GD350-220G-6
185
95
120300
120300
35300
95240
GD350-250G-6
185
95
185300
185300
35300
95240
GD350-280G-6
240
120
240300
240300
70300
120240
GD350-315G-6
95×2P
120
95×2P
150×2P
95×2P
150×2P
95×2P
150×2P
120300
GD350-350G-6
95×2P
150
95×2P
150×2P
95×2P
150×2P
95×2P
150×2P
150300
GD350-400G-6
150×2P
150
150×2P
300×2P
95×2P
150×2P
95×2P
150×2P
150300
GD350-500G-6
95×4P
95×2P
95×4P
150×4P
95×4P
150×4P
95×4P
150×4P
95×2P
150×2P
GD350-560G-6
95×4P
95×4P
95×4P
150×4P
95×4P
150×4P
95×4P
150×4P
95×4P
150×4P
GD350-630G-6
150×4P
150×2P
150×4P
300×4P
150×4P
300×4P
150×4P
300×4P
150×4P
240×4P
Note:
1. Cables of the sizes recommended for the main circuit can be used in scenarios where the
ambient temperature is lower than 40°C, the wiring distance is shorter than 100 m, and the
current is the rated current.
2. The terminals P1, (+), and (-) are used to connect to DC reactors and brake accessories.

Table of Contents