Goodrive350 series high-performance multi-function inverter Chapter 5
-108-
Function
code
Name
Detailed parameter description
Default
value
P00.03
Max. output frequency
P00.03400.00Hz
50.00Hz
P00.06
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via MODBUS communication
9: Set via PROFIBUS / CANopen /
DeviceNet communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse string AB
13: Set via EtherCat/Profinet
communication
14: Set via PLC card
0
P00.11
Acceleration time 1
0.03600.0s
Depend
on model
P00.12
Deceleration time 1
0.03600.0s
Depend
on model
P05.01
P05.09
Digital input function
selection
26: Wobbling frequency pause (stop at
current frequency)
27: Wobbling frequency reset (revert to
center frequency)
/
P08.15
Amplitude of wobbling
frequency
0.0100.0% (relative to set frequency)
0.0%
P08.16
Amplitude of jump frequency
0.050.0% (relative to amplitude of
wobbling frequency)
0.0%
P08.17
Wobbling frequency rise
time
0.13600.0s
5.0s
P08.18
Wobbling frequency fall time
0.13600.0s
5.0s
5.5.17 Local encoder input
GD350 series inverter supports pulse count function by inputting the count pulse from HDI high-speed
pulse port. When the actual count value is no less than the set value, digital output terminal will output
count-value-reached pulse signal, and the corresponding count value will be zeroed out.