Goodrive350 series high-performance multi-function inverter Chapter 9
-264-
Function Address Data description R/W
0006H: Coast to stop (emergency stop)
Communication-based frequency setting (0 –
Fmax, unit: 0.01 Hz)
PID setting, range (0 – 1000, 1000
corresponding to 100.0%)
Communication-based
control command
Communication-based
value setting
In the actual operation, set P00.01 to 2 and P00.06 to 8.
The command transmitted by the master is as follows:
Parameter
address
Inverter
address
Continuous
write
command
Number of
bytes
Parameter
quantity
01 10 20 00 00 02 04
Froward
running
00 01
10 Hz
03 E8
CRC
3B 10
If the operation is successful, the following response is returned:
Parameter
address
Inverter
address
Continuous
write
command
CRC
Parameter
quantity
01 10 20 00 00 02 4A 08
Example 2: Set "Acceleration time" of the inverter whose address is 01H to 10s, and "Deceleration
time" to 20s.
Name Detailed parameter description
Acceleration time is the time needed for accelerating
from 0Hz to max. output frequency (P00.03).
Deceleration time is the time needed from
decelerating from max. output frequency (P00.03) to
0Hz.
Goodrive350 series inverter defines four groups of
acceleration and deceleration time, which can be
selected via multi-function digital input terminal (P05
group). The acceleration/deceleration time of the
inverter is the first group by default.
Setting range of P00.11 and P00.12: 0.0–3600.0s
The address of P00.11 is 000B, 10s is 0064H in the hexadecimal form, and 20s is 00C8H in the