Factory settings
6 720 645 504 (2011/04) en
101
Safety functions Factory setting
Access
level
Setting collector circuit in T10 Lowest permitted temperature E21.T10 -10,0 °C
4,0 °C Groundwater
1
Lowest permitted temperature E22.T10
-10,0 °C
4,0 °C Groundwater
1
Hysteresis alarm reset
1,0K 1
Number of warnings before alarm
11
Setting collector circuit out T11 Lowest permitted temperature E21.T11 -10,0 °C
2,0 °C Groundwater
1
Lowest permitted temperature E22.T11
-10,0 °C
2,0 °C Groundwater
1
Hysteresis alarm reset
1,0K 1
Number of warnings before alarm
11
Tab. 194 Factory settings Safety functions
General Factory setting
Access
level
Set date 0
Set time 0
Summer/winter time Automatic 0
Display backlight intensity 100% 0
Language 0
Country (Start-up) 1
Tab. 195 Factory settings General
Alarms
Factory
setting
Access
level
Alarm indication Alarm buzzer signal Interval
Blocking time
2s
Off
0
0
Alarm indication control unit
Block alarm buzzer No 0
Alarm indication room sensor
Block alarm buzzer
Block alarm indicator lamp
Yes
Yes
0
0
General alarm level Alarms and warnings No 1
Tab. 196 Factory settings Alarm