Settings
6 720 645 504 (2011/04) en
57
16 Settings
16.1 Room temperature
Press the button in the standard display to open the
main menu. Select Room temperature to adjust the
heating.
The following options are available under Room
temperature:
• General
• Circuit 1 Heating
• Circuit 2, 3...
16.1.1 General
Here are:
• Summer/winter operation
• Shut down protection during change over from hot
water to heating
• Minimum outdoor temperature
> Summer/winter operation
>> Circuit 1
>>> Winter operation
If On is selected, the heat pump is constantly in winter
operation and heat and hot water are always produced.
Off signifies constant summer operation; only hot water
is produced. Automatic signifies change-over at the set
outdoor temperature.
>>> Outdoor temperature limit for change over
The menu is displayed only if Automatic has been
selected in Winter operation.
>>> Delay before change over to winter operation
>> Delay before change over to summer operation
>>> Direct start limit for winter operation
When the Use temperature from circuit with highest
temperature function for Circuit 1 is used Circuit 2, 3...
are displayed under Summer/winter operation. The
same settings as for Circuit 1 can be made for each
circuit. The factory settings are the same as for Circuit 1.
Factory setting Automatic
Alternative On/Automatic/Off
Tab. 41 Summer/winter operation
Factory setting 18 °C
Lowest value 5 °C
Highest value 35 °C
Tab. 42 Change over temperature
Factory setting 4h
Lowest value 1h
Highest value 48h
Tab. 43 Delay before change over to winter operation
Factory setting 4h
Lowest value 1h
Highest value 48h
Tab. 44 Delay before change over to summer operation
Factory setting 13 °C
Lowest value 5 °C
Highest value 17 °C
Tab. 45 Direct start limit
In the event of change over between winter
and summer operation and vice versa, there
is a certain delay to prevent constant
starting and stopping of the compressor
when the outdoor temperature oscillates
around the temperature limit.
Below the direct start limit, the control unit
changes over to winter operation without
delay.
Circuit 1 is never allowed to switch over to
summer operation for as long as any circuit
is in winter operation.