16.4 Timers
The control unit shows the timers that are in operation.
There are a number of timers for, e.g., delays of different
types, but also for extra hot water, hot water peak, etc.
A number of these times are set under customer or
installer, whereas others have a set factory value which
cannot be changed. Level shows at what level the setting
can be made. 0 = Customer, 1 = Installer, 3 = Factory.
*)
Between compressors/heat pumps
Timers Setting
Factory
value
Level
Extra hot water Extra hot water duration 0h 0
Hot water peak time for warm-keeping Hot water\Hot water peak\Time for warm-keep-
ing
1,0h 1
Alarm mode delay 1,0h 3
Party Party ( ) 0h 0
Heat pump x timers
> Compressor start delay 10min 3
> Compressor start delay groundwater Heat pump\Groundwater\Compressor start
delay
0s 1
> G2 heat carrier pump stop delay 5min 3
> Block low pressure switch 150s 3
Additional heat timers
> Additional heat start delay Additional heat\Additional heat general\Start
delay
60min 1
> Delay mixing valve control after additional heat start Additional heat\Mixed additional heat\Delay
mixing valve control after additional heat start
20min 1
> Additional heat start delay after high outdoor tem-
perature
Additional heat\Additional heat general\Addi-
tional heat start delay after high outdoor tem-
perature
30min 1
Delay before change over to summer operation Room temperature\General\Summer/winter
operation\Delay before change over to summer
operation
4h 1
Delay before change over to winter operation Room temperature\General\Summer/winter
operation\Delay before change over to winter
operation
4h 1
Shut down protection during change over from hot
water to heating
Room temperature\General 180s 1
Heating start delay
*)
3min -
Heating stop delay
*)
3min -
Tab. 114Timers