94
UMG 96RM-P/-CBM
Status Status description
EEE
bAt
321
Battery capacity is <85%
Operator confirmation required
Message appears weekly after confir-
mation
Battery should be replaced
EEE
bAt
322
Battery capacity is <75%
Battery capacity is too low
Can only be detected after resumption
of mains power
Battery should be replaced
EEE
bAt
330
Battery capacity OK
Message can be acknowledged
Clock is stopped and must be set
EEE
bAt
331
Battery capacity is <85%
Clock is stopped and must be set
Operator confirmation required
Message appears weekly after confir-
mation
Battery should be replaced
EEE
bAt
332
Battery capacity is <75%
Clock is stopped and must be set
Operator confirmation required
Message appears daily after confirmation
Battery should be replaced
Battery monitoring function
The device indicates the condition of the battery via
the "EEE" symbol followed by "bAt" and the status num-
ber. Depending on the status number a confirmation of
the information by the operator may be required. It is re-
commended that the battery be replaced.
Fault number
Battery fault status
Fault message symbol

Other manuals for janitza UMG 96RM-CBM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the janitza UMG 96RM-CBM and is the answer not in the manual?

janitza UMG 96RM-CBM Specifications

General IconGeneral
Brandjanitza
ModelUMG 96RM-CBM
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals