Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
80
Table 26: Menus and Submenus (Continued)
Menu Submenu Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Details
(Figure 31)
Clg > FDD
LowHeatCapAlm (Insufcient Heating
Capability Alarm)
Normal, Alarm
DATCapAlmOffset (DAT Capability
Alarm Offset) / 5.0°F
deg F (1–10)
RefrigType R410A
EVAP-T (Evaporator Temperature) deg F
DischSuperheat1 (Discharge Superheat 1) deg F
SucSuperheat1 (Suction Superheat 1) deg F
LLSubcool1 (Liquid Line Sub-Cooling 1) deg F
SatDischTemp1 (Saturated Discharge
Temperature 1)
deg F
SatLLTemp1 (Saturated Liquid Line
Temperature 1)
deg F
SatSucTemp1 (Saturated Suction
Temperature 1)
deg F
DischSuperheat2 (Discharge Superheat 2) deg F
SucSuperheat2 (Suction Superheat 2) deg F
LLSubcool2 (Liquid Line Sub-Cooling 2) deg F
SatDischTemp2 (Saturated Discharge
Temperature 2)
deg F
SatLLTemp2 (Saturated Liquid Line
Temperature 2)
deg F
SatSucTemp2 (Saturated Suction
Temperature 2)
deg F
Htg > Setup
Htg-En (Heating Mode Enabled For
Operation)
No, Yes
#HtgStgs (Number of Heating Stages
Installed)
0–8
Htg-Type (Heating Control Type) None, Gas, Electric, Hot Water, Steam
HtgOcc-Sp (Occupied Heating Setpoint) deg F (40–85)
Common-SP deg F (45–98)
Auto Changeover delta deg F (2–5)
HtgUnocc-Sp (Unoccupied Heating
Setpoint)
deg F (45–98)
HtgClgSP-Mode (Heat Cool Setpoint
Mode)
Common Setpoint, Individual Setpoints
DAT-Spcong (Discharge Air
Temperature Setpoint Conguration)
Fixed, OA Temp Reset, Supply Fan Reset, Zone
Temp Reset, External
HtgDATUp-SP (Heating Discharge Air
Temperature Upper Setpoint)
deg F (86–135)
HtgDATLo-SP (Heating Discharge Air
Temperature Lower Setpoint)
deg F (85–134)
OAT-ResetSpLower (OAT Reset
Setpoint Lower)
deg F (60–130)
OAT-ResetSpUpper (OAT Reset
Setpoint Upper)
deg F (61–131)
ZT-ResetSpLower (ZT Reset Setpoint
Lower)
deg F (60–130)