Supervisory Signal Event Operation of the Control Panel
IFC-3030 Operations Manual — PN 52026:C 08/05/2005 35
4. Press the SYSTEM RESET soft key to clear any supervisory condition caused by a device with
a latching type code: the supervisory will not automatically clear when the condition causing it
is cleared. Latching supervisory type codes are WATERFLOW S, LATCH SUPERV, and
SPRINKLR SYS.
The panel will send a system normal message to the History buffer, installed printer and
annunciators.
2.6.3 How to Interpret Type Codes
The Type Code that displays in the Supervisory message indicates the function of the point that
initiates the Supervisory. For example, a monitor module with a WATERFLOW S Type Code
means that the module monitors the state of a waterflow switch. If the Type ID code is unfamiliar,
refer to "Software Type ID Codes" on page 63. This appendix is an alphabetical list of Type ID
codes and an explanation of each.