Active Event Operation of the Control Panel
IFC-3030 Operations Manual — PN 52026:C 08/05/2005 37
2.8 Active Event
2.8.1 How the Control Panel Indicates an Active Fire Control Point
A point with a Type ID of FIRE CONTROL is used for air handler shutdown, intended to override
normal operating automatic functions.
Activation of a
FIRE CONTROL point causes the control panel to do the following:
Initiates the monitor module Control-by-Event
Send a message to the panel display, History buffer, installed printer and annunciators
Does NOT light an indicator at the control panel
•Displays ACTIVE in the upper left corner of the LCD, as well as a
FIRE CONTROL Type Code
and other information specific to the device
2.8.2 How the Control Panel Indicates an Active Non-fire Point
A point with a Type ID of NON-FIRE is used for energy management or other non-fire situations.
NON-FIRE point operation does not affect control panel operation, nor does it display a message at
the panel LCD. Activation of a
NON-FIRE point activates CBE—but does not cause any indication
on the control panel. For example, you can program a
NON-FIRE point to turn lights in a zone to a
lower setting when activated. In this case, when the point activates the control panel activates the
point’s CBE to turn the lights down without any audio or visual indication on the control panel.

Table of Contents

Other manuals for Johnson Controls IFC-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-3030 and is the answer not in the manual?

Johnson Controls IFC-3030 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-3030
CategoryControl Panel
LanguageEnglish

Related product manuals