EasyManua.ls Logo

Johnson Controls IFC-3030 - Panel Input;Output Status; Panel Input Status; Panel Output Status

Johnson Controls IFC-3030
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Read Status Panel Input
46 IFC-3030 Operations Manual — PN 52026:C 08/05/2005
3.6 Panel Input
When a Panel Input address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display.
Figure 3.6 Panel Input Screen - Read Status
Display
Lines 1 through 10 - Refer to the descriptions in "Smoke Detector" on page 42.
Line 15 - Current time and date.
3.7 Panel Output
When a Panel Output address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display
Figure 3.7 Panel Output Screen - Read Status
Display
Lines 1 through 10 - Refer to the descriptions in "Smoke Detector" on page 42 with the exception
of line 6. Refer to the section Control Module on page 44 for a description of line 6.
WALK TEST - Displays YES if the device sounds during audible Walk Test.
SILENCEABLE - Displays YES if the operator can manually silence an activated output. The
output resounds for fire.
SWITCH INHIBIT: NO - Displays NO if the operator can manually activate an output.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A FRI SEP 24, 2004
READ ADDRESS: P01.4
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z005 SMOKE CONVEN
Z005, Z027, Z066, , ,
, , , , ,
VERIFY COUNT:0
10:22:34A FRI SEP 24, 2004
BACK
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A FRI SEP 24, 2004
READ ADDRESS: P01.4
AUTOMATIC OFF
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z005 CONTROL
Z005, Z027, Z066, , ,
, , , , ,
WALK TEST: YES
SWITCH INHIBIT: YES
SILENCEABLE: YES - RESOUND FIRE
10:22:34A FRI SEP 24, 2004
BACK

Table of Contents

Other manuals for Johnson Controls IFC-3030

Related product manuals