Software Type ID Codes
64 IFC-3030 Operations Manual — PN 52026:C 08/05/2005
NC SUP L
Indicates latching supervisory conditon, where an open circuit=active. SLC only.
NC SUP T
Indicates tracking supervisory conditon, where an open circuit=active. SLC only
NON FIRE Monitors non fire activations
NONRESET CTL Output unaffected by “System Reset” command
PAS INHIBIT Monitor used to inhibit Positive Alarm Sequence (PAS)
POWER MONITR Monitor for main and auxiliary power supplies
PULL STATION Manual fire-alarm activating device
REL AUDIBLE Activates audio or visual devices steady when releasing starts
REL END BELL Control module used to activate NAC audio or visual device when releasing circuits shut off
REL CKT ULC Control module used to direct outputs to perform a release function as required by ULC
RELAY Form-C relay control module
REL. FORM C Form-C relay that directs outputs to perform a releasing function
RELEASE CKT Directs outputs to perform a releasing function
RESET SWITCH Monitor used to reset the control panel
RF MON MODUL Wireless alarm-monitoring device
RF PULL STA Wireless manual fire alarm-activating device
RFSMOKE(PHOTO) Wireless smoke detector
RF SUPERVSRY Wireless supervisory-monitoring device
SECOND SHOT Monitor module that provides a second manual release for a releasing zone through
connection to a UL-listed pull station
SECURITY L Monitor for activation of latching security alarm
SIL SWITCH Monitor used as Signal Silence switch, turning off all activated silenceable outputs
SMOKE ACCLIM Combination photoelectric/heat detector
SMOKE(ACCLIM+) Combination photoelectric/heat detector with low temperature warning
SMOKE CONVEN Conventional smoke detector attached to an M302MJ
SMOKE DETECT Conventional smoke detector attached to an M302MJ
SMOKE(DUCTI) Duct ionization smoke detector
SMOKE(DUCTP) Duct photoelectric smoke detector
SMOKE(HARSH) HARSH smoke detector
SMOKE(ION) Ionization smoke detector
SMOKE(LASER) Laser smoke detector
SMOKE(MULTI) Multisensor smoke detector
SMOKE(PHOTO) Photoelectric smoke detector
SPEAKER Control module for speaker
SPRINKLR SYS Monitor for a waterflow device
STROBE Control module used with NAC with strobes
SUP L(DUCTI) Duct ionization smoke detector, latching
SUP L(DUCTP) Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, latching
SUP L(ION)** Ionization smoke detector, latching
SUP L(LASER)** Laser smoke detector, latching
SUP L(PHOTO)** Photoelectric smoke detector, latching
SUP T(DUCTI)*, ** Duct ionization smoke detector, tracking
SUP T(DUCTP)*, ** Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, tracking
SUP T(ION)*, ** Ionization smoke detector, tracking
SUP T(LASER)*, ** Laser smoke detector, tracking
SUP T(PHOTO)*, ** Photoelectric smoke detector, tracking
SYS MONITOR Monitor for equipment security
TAMPER Monitor for activation of tamper switch
TELE PAGE Monitor used to emulate the page button on an FFT-7, allowing remote paging to a fire area
TELEPHONE Control module for standard telephone circuit
TRACKING SUPERV Monitor for waterflow tamper switches for alarm points
TROUBLE MON Monitor for trouble inputs
WATERFLOW Monitor for waterflow alarm switch
Software Type ID Code Device
Appendix Table A-1 Software Type ID Codes, Alphabetical List (2 of 3)

Table of Contents

Other manuals for Johnson Controls IFC-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-3030 and is the answer not in the manual?

Johnson Controls IFC-3030 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-3030
CategoryControl Panel
LanguageEnglish

Related product manuals