LX Series Unit Ventilator Controller User's Guide 101
Table 40: Primary Cooling Output
Primary Cooling Output Description
Field cool_output
Measurement Cooling Output
Field Type Category Signed Long
Type Size 2 bytes
Valid Type Range -163.840 – 163.830
Type Resolution 0.005
Units Percent of full scale
Invalid Value 32,767 (0x7FFF)
Raw Range -32,768 – 32,766
0x7FFE
Scale Factor 5, -3, 0
S = a*10b*(R+c)
File Name N/A
Default Value N/A
Table 41: Economizer Output
Economizer Output Description
Field econ_output
Measurement Economizer Output
Field Type Category Signed Long
Type Size 2 bytes
Valid Type Range -163.840 – 163.830
Type Resolution 0.005
Units Percent of full scale
Invalid Value 32,767 (0x7FFF)
Raw Range -32,768 – 32,766
(0 x 8000 – 0 x 7FFE)
Scale Factor 5, -3, 0
S = a*10b*(R+c)
File Name N/A
Default Value N/A