The FIT can save up to seven reports. The information saved to a report is captured
from the current data in the FIT’s memory. Normally only complete and functional FC
Bus installations are saved to Reports but if problems persist during installation
validation a Report could be used to capture and share information about a bus or
bus segment.
Each Report has three types of information stored as follows:
General Bus Information
Device Information
Issue Information
General Bus Information
The General information section of the report is one record and contains the
following information:
Table 1. General Bus Information
Heading Description
Report Name Name of the report entered by the user.
Health The Bus Health Index.
Devices The quantity of devices on the bus.
Idle Volts Differential Voltage Idle. This is + to – voltage reading without
communication.
Idle + + to Com Idle Voltage reading without communication.
Idle - - to Com Idle Voltage reading without communication.
Issues The number of issues reported.
Token Loop ms The recorded Loop Time.
Runtime sec This is the number of seconds from when the FIT was
powered on until the data was captured. The FIT does not
have a Clock. If report date and time is desired the
information must be captured manually.
Report # (Seq
Num)
This is a sequential number the FIT assigns to each report.
Device Information
The Device information section of the report is one record per address discovered.
Some information in this section can only be completed if:
a ScanBus was performed
The device is a Johnson Controls manufactured product.