RDR2S-A and I8O4 Hardware Installation Setup and Adjustments
24-10239-596 Rev. D
32
An RDR2S-A module sharing the same address with a legacy I/O device
(S300-I16, S300-IO8, S300-SIO8 or S300-SI8) must have switch
position SW1-3 or SW1-4 disabled.
The following RDR2S-A reader terminal output points can be re-
assigned:
• Red LED
•Green LED
• Reader Strike
• Reader Shunt
The following RDR2S-A reader terminal input points can be re-assigned:
• Reader Door Contact (on CK721-A controllers, the door is always
reported closed by Soft Alarm Points 18 and 24. On CK722
controllers, disassociating the door contact informs all door-related
features that this door has no door contact)
•Reader REX
Re-assignment of the special RDR2S-A reader terminal output points to
general purpose output points is done by configuring the general purpose
output points listed in the following table:
Re-assignment of the special RDR2S-A reader terminal input points to
general purpose input points is done by configuring the general purpose
input points listed in the following table:
Reader Output Point Terminal Output Point Number
Red LED Output 1 [Open Collector Output]
Green LED Output 2 [Open Collector Output]
Reader Shunt Output 3 [Relay Output]
Reader Strike Output 5 [Relay Output]
Reader Input Point Terminal Input Point Number
Reader Door Contact Input 1
Reader REX Input 2