RDR2S-A and I8O4 Hardware Installation Technical Specifications
24-10239-596 Rev. D
36
TECHNICAL SPECIFICATIONS
The terminal is expected to operate at moderate temperature variation, non-
condensing humidity variation, moderate vibration, and possible dust
contamination.
Item Specification
Input Power +12 to +24VDC or 16 to 24VAC at 24W
Reader Interface 2-wire Wiegand
1
(up to 256 bits)
12VDC, 250mA (typical), 500mA (peak)
Red indicator
Green indicator
1. The RDR2S-A does not support 1-wire Wiegand readers.
General Purpose Inputs Resistive load
Relay Outputs 1A max. 0-24VDC/VAC, 25VA max.
Red LED/Green LED Outputs
2
2. IMPORTANT: These open collector outputs can be damaged with the use of alternating current (AC) poten-
tials as low as 1VAC. The LED outputs can only be connected to direct current (DC) loads up to 24VDC.
50mA max. 0-24VDC
Communications 2 or 3-wire RS-485
Certifications FCC, Class B
CE Mark
C-Tick
Mounting Specifications DIN rail
Flat surface
Dimensions 5.7 H x 5.9 W x 2.2 D inches (14.4 cm x 15.0 cm x 5.5
cm)
Ambient Temperature 32º to 122ºF (0º to 50ºC)
Humidity 10 to 85% non-condensing
Ventilation Cabinets require free movement of air over all
exposed surfaces

Other manuals for Johnson Controls S300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls S300 Series and is the answer not in the manual?

Johnson Controls S300 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelS300 Series
CategoryControl Unit
LanguageEnglish

Related product manuals