Units shall have a separate compartment for electrical controls that can be accessed without
disturbing the unit airflow.
Units shall have a blockoff panel that can be removed to provide interior unit access through
the side of the unit.
Units shall have a removable blockoff panel and a swing away removable electrical panel that
provides sufficient interior unit access for removing the compressor through the side of the
unit.
Unit construction
Units shall be shipped completely wired, piped, and assembled. Wiring pigtails shall be provided
for field control wiring connections. Service valves shall be provided for field refrigerant line
connections.
Units shall be factory leak checked, run tested, and shipped with a holding charge of R-410A
refrigerant.
Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at
a minimum of 500 h under ASTM B117 testing.
Unit base pan shall be stamped G90 equivalent steel finished with powder-coat paint rated at a
minimum of 500 h under ASTM B117 testing.
Units shall have a single corner post opposite the electrical control box and two independently
removable steel coil guard panels to optimize cabinet strength and serviceability.
Units shall have L-shaped stamped sheet metal coil guards with punched and extruded slots for
maximum panel durability and stiffness.
Unit base valves shall be mounted diagonally on the unit base pan with service ports that
provide sufficient clearance for low-loss hose fittings.
Units shall be constructed with a high-pressure switch for system protection.
Units shall be constructed with all badging and labels applied at the factory.
Unit components
Compressor shall be hermetic with internal electrical overload protection and internal
overpressure protection.
Compressor shall be mounted on rubber vibration isolators that do not require the removal of
transportation clips or brackets.
Outdoor fan shall be direct drive with vertical air discharge for low sound levels.
Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors
approved for vertical shaft applications.
Outdoor coil shall be air cooled and have zinc-coated aluminum microchannel construction for
small size and low weight.
Unit warranties
Unit manufacturer shall provide a 10-year compressor warranty without a requirement for unit
registration.
Unit manufacturer shall provide a 5-year parts warranty without a requirement for unit
registration.
75Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TCD2B18S21S and is the answer not in the manual?

Johnson Controls TCD2B18S21S Specifications

General IconGeneral
BrandJohnson Controls
ModelTCD2B18S21S
CategoryAir Conditioner
LanguageEnglish

Related product manuals