EasyManua.ls Logo

Johnson Controls UNT110-1 - Page 80

Johnson Controls UNT110-1
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80
UNT Controller—Unitary (UNT) Controller
Table 38: Recommended Transformers
Transformer Type Power Description
Johnson Controls Y65 Series
40 VA 120 VAC to 24 VAC
Johnson Controls Y65G13-0
40 VA 24 VAC to 24 VAC
Johnson Controls AS-XFR050-0
50 VA 120 VAC to 24 VAC
(insulated split-bobbin
windings, high noise
immunity, resettable breaker)
3. Drive rooftop unit loads via pilot relays (see Figure 40) if any of
the following conditions exists:
The rooftop unit contains any contactor/relay coils that might be
energized by some means other than directly by the UNT’s
binary outputs. A common example of this is a time delay relay
contact closure in a BO circuit.
An individual BO load exceeds 800 mA.
All loads together will cause the UNT to require more than
40 VA of 24 VAC power when mounted in an enclosure, or more
than 75 VA when mounted in a well-vented open area.
Voltages other than 24 VAC need to be switched.
Note: Install pilot relays for isolation between the UNT and the
rooftop unit contactors/relays.
4. You may drive rooftop unit contactor/relay loads directly
(see Figure 39) if all of the following conditions exist:
Under normal operation, the UNT binary outputs directly drive
all contactor/relay coils within the rooftop unit.
Individual BO loads exceed 50 mA. (Required to keep the
triac on.)
Individual BO loads do not exceed 800 mA.
The UNT and all its loads together draw less than 40 VA of
24 VAC power when mounted in an enclosure, or less than
75 VA when mounted in a well-vented open area.
Triac load voltage is 24 VAC
±
5%.
Note: Connect the UNT binary outputs (triacs) to the rooftop unit
terminal strip.

Table of Contents

Related product manuals