POINT ID POINT DESCRIPTION
N2
OBJECT
READ
( R )
WRITE
( W )
VALUE
RANGE
(ANALOG
ONLY)
UNIT
(ANALOG
ONLY)
IN-
STANCE
NUMBER
COMMENTS
UNIT
ENABLE
NETWORK UNIT START
1 = ENABLE
0 = DISABLE
BYT44 R,W - - 15001
SATACSP
SUPPLY AIR COOLING
TEMPERATURE SET
POINT
ADF45 R/W
48.0
– 70.0
DEG F 16001
RATACSP
RETURN AIR COOLING
TEMPERATURE SET
POINT
ADF46 R/W
55.0
– 80.0
DEG F 16002
SATHTSP
SUPPLY AIR HEATING
TEMPERATURE SET
POINT
ADF47 R/W
80.0
– 125.0
DEG F 16003
RATHTSP
RETURN AIR HEATING
TEMPERATURE SET
POINT
ADF48 R/W
50.0
– 80.0
DEG F 16004
O/A MIN POS
OUTDOOR AIR MINIMUM
POSITION SETPOINT
ADF49 R/W 0 – 100 % 16012
ONLY WITH AIR SIDE ECONO-
MIZER
SAP SP
DUCT STATIC PRESSURE
SET POINT
ADF50 R/W 0.0 – 2.0 IN OF WC 16013 ONLY WITH VAV OR FLEXSYS
AI = ANALOG INPUT
BI = BINARY INPUT
AO = ANALOG OUTPUT
BO = BINARY OUTPUT
ADF = ANALOG DATA FLOAT
ADI = ANALOG DATA INTEGER
BYT = DATA BYTE
TABLE 19 – N2 POINTS LIST
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York VERSECON YSWD Series and is the answer not in the manual?

Johnson Controls York VERSECON YSWD Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork VERSECON YSWD Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals