JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
Continued on next page
TABLE 18 – BACnet MS/TP points (CONT.)
Point ID Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
FCVFDMod
Indicates if the VAV Modulating
Output is Forced On:
1 = On – Active
0 = Off – Inactive
BBV R - - 15516
Freeze
Hydronic Coil Freezestat
Alarm:
1 = Fault – Active
0 = No Fault – Inactive
BBV R - - 15102
Only with Hydronic
Heat
Freeze Stat
Freeze Stat Input:
1 = Closed – Active
0 = Open – Inactive
BBI R - - 12006
Only with Hydronic
Heat
FRIDAYSCHED1
Turns the Friday Schedule 1
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 878
FRIDAYSCHED10
Turns the Friday Schedule 10
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 978
FRIDAYSCHED11
Turns the Friday Schedule 11
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 989
FRIDAYSCHED12
Turns the Friday Schedule 12
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 1000
FRIDAYSCHED13
Turns the Friday Schedule 13
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 1011
FRIDAYSCHED14
Turns the Friday Schedule 14
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 1022
FRIDAYSCHED15
Turns the Friday Schedule 15
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 1032
FRIDAYSCHED16
Turns the Friday Schedule 16
On and Off:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 1043