DC Power Electrical Safety Guidelines
A DC-powered device is equipped with a DC terminal block that is rated for the power requirements of
a maximally configured device.
Incorporate an easily accessible disconnect device into the facility wiring. Be sure to connect the ground
wire or conduit to a solid office earth ground. A closed loop ring is recommended for terminating the
ground conductor at the ground stud.
Run two wires from the circuit breaker box to a source of 48 VDC.
A DC-powered device that is equipped with a DC terminal block is intended only for installation in a
restricted-access location. In the United States, a restricted-access area is one in accordance with Articles
110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.
NOTE: Primary overcurrent protection is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.
Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
For personal safety, connect the green and yellow wire to safety (earth) ground at both the device and
the supply side of the DC wiring.
The marked input voltage of –48 VDC for a DC-powered device is the nominal voltage associated with
the battery circuit, and any higher voltages are only to be associated with float voltages for the charging
function.
Because the device is a positive ground system, you must connect the positive lead to the terminal
labeled RTN, the negative lead to the terminal labeled –48 VDC, and the earth ground to the device
grounding points.
181

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper EX4650 Series and is the answer not in the manual?

Juniper EX4650 Series Specifications

General IconGeneral
CoolingFront-to-back or back-to-front airflow
Rack Units1U
MAC address table size288, 000 entries
Memory16 GB
Storage64 GB SSD
Power SupplyDual redundant, hot-swappable
Junos OSSupported
Jumbo frames9216 bytes
Operating temperature0°C to 40°C (32°F to 104°F)
Input voltageAC: 100-240V
FansHot-swappable, redundant
Operating humidity5% to 90% (non-condensing)
Ports48 x 10GbE SFP+/SFP28 ports 8 x 40GbE QSFP+/100GbE QSFP28 ports

Related product manuals