6.0 Annex C Protection from Electromagnetic Interference
As per any other electronic equipment, the RAC 4XT can be affected by electromagnetic inter-
ference caused by industrial electrical equipment such as elevator motors.
To prevent the unit from operational instability such as "freezing" or losing programming, shei-
lded cables should be used and connections made as per the diagram below.
1- Use shielded cables for the readers
2- Connect the shield wire of the reader cable to the Ground wire
3- Connect the wires to the Mounting screw of the RAC.
(Remove the paint under the mounting screw of good electrical contact.)
4- Ensure the Relay Expansion Board (if applicable) has no more than 30VDC from elevator
or other power source.