KaControl for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
19
Door air curtains 1.96
Door air curtain with KaController
Maximum 6 door air curtains
6.2 Single-circuit Controls of up to 6 Units
Maximum permissible cable lengths
Total length of bus cables between door air curtains max. 30m
Total length of bus cable between room control unit and master unit max. 30m
Total length between door air curtain and external potential-free contacts max. 30m
e.g. external thermostat, ext. contact ON/OFF etc.
Optional: - External thermostat for summer
mode / winter mode changeover
- external contact ON/OFF
KaController
Type 3210001
Type 3210002
KaController
#1
#2
#3
#4
#5
#6
GND
Rx+/Tx+
Rx-/Tx-
GND
GND
GND
V+
Tx
Tx
GND
V+
Tx
Tx
GND
V+
Tx
Tx
GND
V+
Tx
Tx
GND
V+
Tx
Tx
24 V
GND
GND
GND
GND
GND
V+
Tx
Tx
GND
The number of connecting wires required incl.
fuses is given on the individual control units.
* Lay shielded cables (e.g. Y(ST)Y, 0.8 mm), separately
from high-voltage cables.
** Lay shielded, paired cables, e.g. CAT5 (AWG23) of
at least the same value, separately from high-voltage
cables.
Master unit
#1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
Slave unit
#2
Slave unit
#3
Slave unit
#5
Slave unit
#4
Slave unit
#6
Mains
230 V/50 Hz
Max. length of
bus line = 30 m
Max. length of bus line = 30 m
Max. length of bus line = 30 mMax. length of bus line = 30 m
Diagram of bus cabling
Mains
230 V/50 Hz
Mains
230 V/50 Hz
Mains
230 V/50 Hz
Mains
230 V/50 Hz
Mains
230 V/50 Hz
2**
2**
2**
2**
2**
2**
3
3**
3 3 3 3
3