KaControl for Door Air CurtainsINSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATION AND OPERATING INSTRUCTIONS
1.96
40
Door air curtains
The polarity of the digital input DI2 is set using parameter P56 when DIP switch no. 4 is set to ON.
Function Standard Min Max Unit
P56 Polarity of DI2 when DIP2=ON (Heating/Cooling changeover via DI2) 102
0 = Contact closed . . . . . . . . --> heating
Contact open . . . . . . . . . --> cooling
1 = Contact open . . . . . . . . . --> heating
Contact closed . . . . . . . . --> cooling
11.3.7 Locking Operating Options or Functions, Parameter 38
Parameter P38 can be used to lock individual operating options or functions.
Function Standard Min Max Unit
P38 Locking operating options or functions 105 0 255
Every operating option or function is
allocated a defined value.
The values of the locked operating
options or functions must be added
together and assigned to parameter
P38.
Value
Automatic operating mode 1
Cooling mode 2
Real-time clock 4
Ventilation-only operating mode 8
Heating
mode 16
Automatic fan function 32
Eco/Day function 64
Timer programs 128
Example: Locking
- Eco/Day function
Value
Automatic operating mode 11-
Cooling mode 2-
Real-time clock 4-
Ventilation-only operating mode 88-
Heating
mode 16 -
Automatic fan function 32 32-
Eco/Day function 64 64
Timer programs 128 -
Parameter P38 setting 105
(default)