KaControl for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
21
Door air curtains 1.96
6.4 Inputs for Processing External Contacts (e.g. external
thermostat, ON/OFF etc.)
All door air curtain master units have multifunctional inputs that
can be assigned different functions during commissioning.
Connect up the cables in accordance with the wiring diagram and
configure the functions using the KaController.
The maximum cable length between the master unit and the
external potential-free contacts is 30 metres.
No external contacts (e.g. external thermostat, ext. contact ON/OFF
etc.) can be connected to the slave units.
** Use shielded, paired cables, e.g.
CAT5 (AWG23) of at least the
same value
Master unit
#1
Mains
230 V/50 Hz
Mains
230 V/50 Hz
Slave unit
#2
Max. cable
length = 30 m
2**
2**
2**
33
2**
KaControl
C1
KaControl
C1