MULTICA21 & flowIQ® 2101 /..02 /..03 TECHNICAL DESCRIPTION
Kamstrup A/S •Technical Description • 5512-897_J1_GB • 06.2016 27
6.1 Configuration - flowI 2103
KK
LLL
MMM
N
P
R
S
T
□□
□□□
□□□
Target date (FIXED)
01
Average time of max values
2 minutes
002
Customer label 2005-MMM
MMM
Leakage message limit
[l/h] For meter sizes - Qn = 1.5 2.5
OFF
-
-
0
Flow continuously > 0.5 % of Qn
8
13
1
Flow continuously > 1.0 % of Qn
15
25
2
Flow continuously > 2.0 % of Qn
30
50
3
Flow continuously > 0.25 % of Qn
3.8
6.3
4
Flow continuously > 0.1% of Qn
2
3.2
5
Pipe burst limit
[l/h] For meter sizes - Qn = 1.5 2.5
OFF
-
-
0
Flow > 5 % of Qn for 30 minutes
75
125
1
Flow > 10 % of Qn for 30 minutes
150
250
2
Flow > 20 % of Qn for 30 minutes
300
500
3
Optional register in data logger
Monthly target volume/Min.temp.water, daily/Time weighted average temp. meter, daily
3
Monthly target volume / Min. water temp. monthly / Min. temp. meter,latest month
5
Monthly target volume/Min. water temp., monthly/Max temp. meter, latest month
7
Daily max flow / Min.temp.water, daily / Time weighted average temp. meter, daily
9
Display resolution
00001 m³
0
00000.1 m³
1
00000.01 m³
2
00000.001 m³
3
Encryption level
No encryption
0
Utility encryption (only available for selected markets)
2
Encryption with separately forwarded key
3
Unless otherwise stated in the order,
Kamstrup supplies the following:
01
002
000
1
3
7
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 21 and is the answer not in the manual?

Kamstrup MULTICAL 21 Specifications

General IconGeneral
BrandKamstrup
ModelMULTICAL 21
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals