EasyManua.ls Logo

KBR multicomp F144-MS-1V1C1TI6DO6RO-3 - Page 55

KBR multicomp F144-MS-1V1C1TI6DO6RO-3
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rev. 1.00
22586_EDEBDA0253-0318-1_EN
55
KBR multicomp F144-3 6DO/6RO
Address Words Description Value Format
0xD020 2 Byte sequence for oat on the Modbus
(1=as dened // 0=reversed)
0-1 unsigned
long
0xD022 2 Frequency correction (0=Auto // 1=50
Hz // 2=60 Hz)
0-2 unsigned
long
0xD024 2 Stage monitoring (0=No) 0 unsigned
long
0xD026 2 Temperature measurement (1=Yes //
0=No)
0/1 unsigned
long
0xD028 2 Fan relay
(1=available // 0=not available)
0/1 unsigned
long
0xD02a 2 Temperature [0.1 °C] that triggers the
fan when the threshold is exceeded
0-700 unsigned
long
0xD02c 2 Temperature [0.1 °C] that causes the fan
to switch o when the value falls below
the threshold
0-700 unsigned
long
0xD02e 2 Temperature [0.1 °C] that triggers the
stages when the value falls below the
threshold
0-700 unsigned
long
0xD030 2 Temperature [0.1 °C] that causes the
stages to switch o when the threshold
is exceeded
0-700
unsigned
long
0xD032 2
0xD034 2
0xD036 2
0xD038 2
0xD03A 2
0xD03C 2
0xD03E 2
0xD040 2 Switching performance
0xD042 2 Percentage of smallest available stage
before activation
70-150 unsigned
long
0xD044 2 Percentage of smallest available stage
before stages can be switched o
70-150 unsigned
long
0xD046 2 Time before message "PFC too small" is
displayed [s]
3-3000 unsigned
long
0xD048 2 Idle time after compensation [s] 0-30 unsigned
long
0xD04A 2 Thyristor idle time after compensation
[ms]
20-9999 unsigned
long
0xD04C 2 Contactor switching interval [s] 0-10 unsigned
long