Rev. 1.00
22586_EDEBDA0253-0318-1_EN
14
KBR multicomp F144-3 6DO/6RO
3 Setting range of the
congurable parameters:
Stage state:
Stage switching mode Automatic, Manual o, Manual on
Commissioning:
Password 4 digits, numerical, no password = 9999
(meaning all functions are accessible)
Primary current 1 A to 999999A
Secondary current 1 and 5 A
Consumption target cosφ ind. 0.80 to cap. 0.80
Recovery target cosφ ind. 1.0 (cannot be congured)
Primary voltage 1 V to 999999 V Ph-Ph
Secondary voltage 1 V to 999 V Ph-Ph
Thyristor stage discharge time 20 to 9999 ms
Contactor stage discharge time 0 to 900 seconds
Max. stage power per
switching cycle 0 to 9999 kvar
Rot. eld U L1N, L2N, L3N, L12, L23, L31
Rot. eld I L1, L2, L3, -L1, -L2, -L3
Stage power learning mode Yes, No
Stage power 0 to 999.9 kvar
Switching performance:
Hysteresis connection 70 to 150 %
Hysteresis switch-o 70 to 150 %
Alarm relay time 3 to 3000 sec.
Thyristor stage idle time 20 to 9999 ms
Contactor stage idle time 0 to 300 seconds
Thyristor stage switching interval 50 to 9999 ms
Contactor stage switching interval 0 to 10 seconds
FTS alarm cosφ ind. 0.70 to 1.00
Attenuation coecient Qmiss 0 to 9
Voltage attenuation coecient 0 to 9
Current attenuation coecient 0 to 9