KBR multicomp F144-3 6DO/6RO
Address Words Description Value Format
0xD11E 2 0 unsigned
long
0xD120 2 Base index for the following stage
parameters
(addresses 0xD120 to 0xD12E)
10 (= stage 11) unsigned
long
0xD12E 2 0 unsigned
long
0xD130 2 Base index for the following stage
parameters
(addresses 0xD130 to 0xD13E)
11 (= stage 12) unsigned
long
0xD13E 2 0 unsigned
long
Request:
01 04 D0 01 00 02 xx xx
in which
01 Device address
04 Command
D0 01 Read from register 0xD002 "Measuring voltage primary trans-
former" (in accordance with the Modbus denition, the required
address must be set to -1 in the request telex)
00 02 Read 2 registers, i.e. read 1 data point
xx xx CRC code
Response:
01 04 04 xx xx xx xx yy yy
in which
01 Device address
04 Command
04 4 data bytes
xx xx xx xx Measuring voltage primary
transformer
400V
yy yy CRC code