28
This function acts as an adjustable current limit when operating at a con-
stant speed.  It can be used to prevent the load current from exceeding the 
inverter's over current level, thereby preventing shut down of the inverter 
with an E.OC fault. When the load level reaches the adjusted value, the 
output frequency is reduced until the load drops below the adjusted value,  
after which the frequency is increased again to the previous value.  Setting 
the value too low may prevent the motor from running at the desired speed. 
CP. 3 displays "SSL" when the function is active.
Adjustment range:  0...200 % (off)
Resolution:  1 %
Factory Setting:  200 % (off)
f
set
f
actual
on
off
on
off
CP.25
CP.24
LAD-stop
Current limit
t
t
t
Max. constant 
current
Utilization
This  function  acts  as  an  adjustable  current  limit  during  acceleration  or 
deceleration. It can be used to prevent the load current from exceeding the 
inverter's peak current rating, thereby preventing shut down  with an E.OC 
fault. When the load level reaches the adjusted value, the acceleration or 
deceleration is stopped until the load drops below the adjusted value.  Note: 
if this parameter is adjusted too low, the motor may not be able to accelerate 
to full speed. The motor will run at a low speed. CP.3 displays "LAS" when 
the function is active.
Adjustment range:  0...200 %
Resolution:  1 %
Factory setting:  140 %
Max. ramp current
Special Adjustments