Installation - 3 
49 
Application Connections 
Local Sense Connections 
Figure 3-10 illustrates a typical setup with module number 1 connected for constant current or constant 
resistance operation.  Local sensing is used in applications where lead lengths are relatively short, or where load 
regulation is not critical.  The sense switch must be set to LCL.  Load leads should be bundled or tie-wrapped 
together to minimize inductance. 
 
Figure 3-10.  Local Sensing 
Remote Sense Connections 
Figure 3-11 illustrates a typical setup with module number 1 connected for remote sense operation.  The remote 
sense terminals of module 1 are connected to the output of the power supply.  Remote sensing compensates for 
the voltage drop in applications that require long lead lengths.  This is only useful when module 1 is operating in 
CV or CR mode. Remote voltage sensing also provides greater accuracy when using voltage readback in all 
operating modes.  The sense switch must be set to RMT.  Load leads should be bundled or tie wrapped together 
to minimize inductance. 
Parallel Connections 
Figure 3-12 illustrates how modules can be paralleled for increased power dissipation.  Up to six modules in one 
mainframe can be directly paralleled in CC or in CR mode. Modules cannot be paralleled in CV mode.  Each 
module will dissipate the power it has been programmed for.  For example, if two modules are connected in 
parallel, with module number 1 programmed for 10 A and module number 2 programmed for 20A, the total 
current drawn from the source is 30 A.