EasyManua.ls Logo

Kidde Stratos-HSSD 2 - 11.6 Flow fault errors; 11.8 No display

Kidde Stratos-HSSD 2
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 48
Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
11.6 Flow fault errors
These occur when the airflow rate into the detector exceeds the pre-programmed
parameters. As the detector ‘learns‘ the flow setup from the initial installation, this
usually means that there has been some change in conditions. A Flow high fault
may indicate that a sampling pipe is damaged, and a Flow low fault may indicate
that the pipe has been blocked, e.g. by nearby building operations.
If the detector input is sampled from one area and the exhaust is in another area
with different pressure (e.g. the detector is in a roof space and sampling from an
enclosed room), this may lead to flow faults. In this case it would be necessary to
lead a pipe from the exhaust to the protected area to ensure nominal flow.
11.7 Cannot refit the front cover
Check that the recessed top edge of the cover is securely located behind the
locating guard rails on the chassis (see section 5.2.1).
Check that the key is turned to the unlocked position (anticlockwise)
11.8 No display
Check that the display ribbon cable is securely connected to the detector/
command module main board and to the display board as appropriate. (see
section 5.2.1)
Check that the display ribbon cable has not been damaged.
11.6.1 “Low flow” error messages.
Check that the pipe giving the error is not blocked
Check that, if the pipe is unused, the flow sensor for this pipe has been disabled
(see section 3.4.30)
Check that the low flow fault threshold is not set too high (see section 3.4.30)
Consider increasing the aspirator (fan) speed (see section 3.4.28)
11.6.2 “High flow” error messages
Check that the pipe is pushed home into the inlet and is not broken or cracked
Check that installed pipework is fitted with an endcap.
PipeCAD
®
pipe modelling software prompts the use of appropriate endcaps. Open
bore pipes are not recommended.
Check that the high flow fault threshold is not set too low (see section 3.4.30)
Consider reducing the aspirator (fan) speed (see section 3.4.28).

Related product manuals