TM0024 Page 11 of 33 Issue 2.01
To gain entry from any type 2 repeater into access level 2, operate any numeric key
once and the password prompt will appear on the display as shown in figure 2.3.
Enter the required access level 2 4-digit password number and then operate the
Enter key. Once selected the panel will then verify the entry, which will either be
accepted or rejected. Each operation of a membrane key will have audible and
visual confirmation by a short operation of the internal panel buzzer and entry of the
number will be shown on the display as a “#”, for security reasons.
STATUS
Sat 30 Mar 96
NORMAL
Select Password
Figure 2.3
Upon acceptance of the entered password the control panel will request an entry of a
numeric key, upon which the options which are capable of being selected at access
level 2 will be displayed as per table 2.0. Figure 2.4 shows the top-level menu
features, which are capable of being selected when the access level 2 password is
selected.
Access Level 2 Main menu
Isolate
List
Set
Select option using and
figure 2.4
Silence Buzzer
The operation of this key is switch selectable, dependant upon the selection,
operation of the key will either allow local or a global silence of the internal buzzer,
refer to section 1.5.1 for further information. When set to the global selection,
operation of the key is used to Silence all of the internal panel buzzers which are
connected to the main control panel. Selection to the local position will only allow
silencing of the local internal buzzer only.
Upon activation of the internal panel buzzer, operation of the Silence Buzzer
membrane key will deactivate the buzzer. When the key is operated a text message
will be displayed for a short time period confirming the operation as shown in figure
2.5.