TM0024 Page 4 of 33 Issue 2.01
The repeater panel maybe supplied with a 24 zonal Fire and Fault LED membrane,
which is capable of being expanded in increments of 32 indications to a maximum of
120. Each indication is capable of having text printed on to its associated slider
insert, which can match the programmed zone text. Each zone slider is capable of
being removed and inserted from the top edge of each membrane, this is to cater for
site specific information.
When an activation of either fire or fault occurs the relevant zonal led will illuminate.
When a zonal fire condition occurs the zonal, red, fire LED will pulse until it is
silenced upon which it will become constant and will clear upon reset. Operation of a
zonal fault will cause the yellow fault LED to operate in a pulsed mode until the fault
condition automatically clears or the control panel has been Reset.
The Status LED indications provide visual indication of the condition of the control
panel and are designed in accordance with the requirements of EN54-2, refer to
TM0001 figure 1.0 for further information. The status indicators have slider inserts
are capable of being removed and altered to cater for different languages.
1.2 SOUNDER CIRCUIT
The Repeater panels are supplied as standard with a single monitored sounder
circuit positioned on the main repeater terminal PCB (44782-K078), which is rated at
1 amp at 24 volts DC
.
The sounder circuit is capable of being programmed with
specific site configuration information to operate as required. If the sounder circuit
has not been programmed then it will operate in a default operation for any Fire or
Evacuate conditions and will remain active until silence alarms. The operation is also
controlled by the set up switches located on the Main Processor card part number
44782-K077, refer to section 1.5.1 for further information.
1.3 RELAY OUTPUTS
The Control panel is supplied as standard with a single VFCO relay which is rated at
1 amp at 30 volts dc, which is positioned on the main repeater terminal PCB (44782-
K078. The relay is capable of being programmed with specific site configuration
information to operate as required. If the relay is not programmed then they will
operate for any Fire or Evacuate condition and will remain active until panel reset.
A Fault Relay rated at 1 amp 30 v dc is also supplied which is normally energised
during status normal and when any fault condition is detected the relay will de-
energise. Note that this relay will automatically re-energise when non latching fault
conditions automatically clear.