TM0024 Page 8 of 33 Issue 2.01
CHAPTER 3
REPEATERS WITH CONTROLS
3. DESCRIPTION
Repeaters with controls are allocated by the selection of an address “1 to 15" via the
address switch. Located on the main processor card (44782-K077), refer to section
1.5.1 for further switch information. A maximum of 15 repeaters with controls can be
connected to the main control panel. Each repeater panel is capable of having a
location name assigned against the repeater address via the main control panel
programming.
The repeaters with user controls have the facility for a monitored sounder circuit and
a VFCO relay, these circuits are fully programmable via the main control. If the
circuits have not been programmed they will have a default operation by activating for
any priority “0" or “1" activation form the main control panel. The monitored circuit will
remain activated until the main panels “Silence Alarm” key is operated at which point
the sounder circuit will de-energise. The VFCO relay will de-energise upon the
operation of the “Panel Reset”. Once the outputs have been programmed they will
operate as per the program. Fault conditions detected by the repeater panel will be
transmitted back to the main control panel.
The repeater panels maybe configured with or without status and zonal indications,
Input/ Output extension cards and internal panel printer. The inclusion of these
options will determine the enclosure dimensions.
3.1 CONTROLS
The operation of the control keys are detailed within the Access section, refer to
section 3.2 for control key operation. The control section has a removable slider
insert which allows the user to carry out language translations.