TM0024 Page 7 of 33 Issue 2.01
CHAPTER 2
RECEIVE ONLY REPEATERS
2. DESCRIPTION
Receive only repeaters which have no controls are determined by the selection of the
address “0" via the address switch, which is located on the main processor card
(44782-K077), refer to section 1.0 for further switch information. A maximum of 49
repeaters without controls are permitted to be connected to the main control panel.
Receive only repeaters have the facility for an internal monitored sounder circuit and
a VFCO relay, these will operate in a common operation for any priority “0" or “1"
activation. The monitored circuit will remain activated until the main panels “Silence
Alarm” key is operated at which point the sounder circuit will de-energise. The VFCO
relay will de-energise upon the operation of the “Panel Reset”. Fault conditions
detected by the repeater panel will not be transmitted back to the main control panel
and will be displayed on a local basis only.
The repeater panels maybe configured with or without status and zonal indications,
Input/ Output extension cards and internal panel printer. The inclusion of these
options will determine the enclosure dimensions.
2.1 CONTROLS
A receive only repeater is not capable of having any effect over the operations of the
main control panel. The user keys are accessible at all times and are classed as
access level 1 operation.
Silence Buzzer
The operation of this key is switch selectable refer to section 1.5.1 for further
information. Operation of the switch will allow the deactivation of the internal buzzer
and dependant upon the switch selection may deactivate the local sounder circuit.
Test
The Test key is used to test the LCD, LEDs, internal buzzer and the control keys of
the repeater. This key maybe operated at any time and will initiate the test condition.