Appendix C: Applications 
230  P/N 3102351-EN • REV 005 • ISS 28DEC18 
RM1 Riser Monitor module. You can also use a CT1 module and a PAM-1 control relay for this 
purpose. In addition a G1M-RM is required for synchronization. 
Figure 60: Typical wiring for a system alarm signaling application 
 
  SLC IN − 
  First detector 
  Last detector 
  JP1:L 24 VDC monitor 
(8)  SLC OUT − 
(9)  Active 
(10)  Normal 
(11)  AUX riser 24 VDC + 
 
Notes 
•  A polarity reversal module can be used to provide power to the sounder bases. You can omit the polarity 
reversal module if correlation groups are used to activate the sounder bases. 
•  The RM1 module is used to monitor riser polarity. You can also use a CT1 module and a PAM-1 control relay 
for this purpose. 
•  The G1M-RM module is required to provide sounder synchronization. 
Programming sounder bases for a local alarm signaling 
application 
Note: For PS/PD, PHS/PHD, IPHS, and SD detectors configured as “Supervisory Non-
latching” device type or for PCOS/PCD detectors (smoke element) configured as “Smoke 
Supervisory Non-latching” device type, if the base is Relay/Sounder, then the follow type 
option cannot be configured as “Head.” The follow type in this case should be set to “Alarm.”