Chapter 4: Reports 
170  P/N 3102351-EN • REV 005 • ISS 28DEC18 
To view device serial numbers: 
1.  Press the menu button and choose Reports. 
2.  Choose Device Details. 
3.  Choose Serial #. 
Diagnostics reports 
There are two Diagnostics reports designed to show the communication performance of the 
devices on a loop. 
Comm Retries report 
This report lets you display a list of devices that have required two, three, or four consecutive 
communication poll retries. It lists the devices that could potentially generate a communication 
fault by showing the maximum number of retries for the current hour and a summary of the 
past 24 hours. 
The report can be used to identify devices with intermittent communication faults. A device 
appearing in this report is an indication that the wiring to the device is suspect. To investigate 
problem devices, inspect the wiring between the problem device and another device not in the 
report. Inspect this section of wiring for problems such as loose connections and intermittent 
wiring breaks. 
Note: The current hour retries can be cleared and updated by running the Loop Comm Check 
diagnostic. (See “Loop comm check” on page 176 for more information.) 
Response Quality report 
This report lists the devices that are communicating at or below a quality percentage that you 
specify. By entering different percentages, you can troubleshoot device communications on a 
loop. 
The panel periodically stores the measurement of the response for individual devices during 
communication polling. The report displays the result of the latest poll as a percentage, where 
100% is the best response (maximum possible pulse strength) and anything less than 44% 
means that the device failed a communication poll and could potentially generate a 
communication fault. 
Devices appearing in this report are an indication that the wiring to the devices is questionable 
or that the devices themselves are questionable. To investigate problem devices, inspect the 
wiring between the problem device and another device not in the report. Inspect the wiring for 
problems such as exceeding wiring specifications (see “Addressable device loop wiring” on 
page 12 for more information), loose connections, and intermittent wiring breaks and shorts.