Chapter 2: Front panel programming 
P/N 3102351-EN • REV 005 • ISS 28DEC18  35 
UL/ULC programming requirements 
 
 
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED 
PARTIES
 
This product incorporates field
-programmable software. In order for the product to comply with the requirements 
cy, certain programming features or options must be limited to specific values or not used at all 
 
 
Programmable 
feature or option
 
Possible settings  Listing 
Agency 
Permitted  
(Y/N) 
Permitted 
settings 
Panel default 
  0 to 15 hours  UL, ULC  Y  1 to 3 hours  3 hours 
Telephone line cut 
supervision duration
 
1 to 120 seconds  UL, ULC  Y  10 to 120 seconds  120 seconds 
Transmission test 
frequency
 
0 to 240 hours  UL 
ULC 
Y 
Y 
6 hours 
24 hours 
6 hours 
6 hours 
  Off or 5 to 30 minutes  UL 
ULC 
Y 
N 
5 to 30 minutes 
Off 
Off 
  Dual line 
Single line 
Modem only 
None 
UL, ULC  Y  Dual line 
Single line [2] 
Modem only [3] 
None [3] 
Dual line 
  5 to 10  UL, ULC  Y  5 minimum  5 retries 
  1 to 45 seconds  UL, ULC  Y  Yes  5 seconds 
Send event restore 
codes [1]
 
No or Yes  UL, ULC  Y  Yes  Yes 
  Off or 1 to 255  UL, ULC  N  Off  Off 
  On or Off  UL, ULC  Y  On  On 
Supervisory setting 
for Smoke detectors/
 
smoke element of 
combination 
detectors 
that trigger 
 
Smoke Alarm, Smoke 
verified, Supervisory 
latching, Supervisory 
nonlatching 
UL, ULC  N  Smoke Alarm, 
Smoke verified. 
Exception: 
Supervisory 
permitted as per UL 
864 
 Smoke Alarm 
[7] 
  1 to 4 modes  UL, ULC  Y  1 or 2 modes  1 mode 
  0, 10, 20, 30 seconds  UL, ULC  Y  0 to 30 seconds  10 seconds