Chapter 2: Front panel programming 
36  P/N 3102351-EN • REV 005 • ISS 28DEC18 
Programmable 
feature or option
 
Possible settings  Listing 
Agency 
Permitted  
(Y/N) 
Permitted 
settings 
Panel default 
  0 to 300 seconds 
through release 
correlation; 10, 20, 30, 
40, 50 seconds on REL 
module 
UL, ULC  Y  0 to 60 seconds 
(combined) 
0 seconds in 
release 
correlation; 50 
seconds on 
REL module 
  0 to 300 seconds 
through abort 
correlation: 0, 10 
seconds on REL 
module 
UL, ULC  Y  0 to 60 seconds 
(combined) for all 
abort modules 
0 seconds in 
abort 
correlation; 10 
seconds on 
REL module 
Carbon monoxide (CO) 
signaling
 
 
Input: (CO element of 
the detector): 
CO Alarm 
CO Supervisory 
CO Monitor 
Output: Channel 2 of 
T3T4 module 
UL, ULC  Y  Input: (CO element 
of the detector) [5]: 
CO alarm 
Output: Channel 2 
of T3T4 module 
No default 
correlation 
 with a 
 
         
Zone event 
notification Type 
 
Alarm, Monitor, 
Supervisory, Waterflow 
 
Alarm, Monitor, 
Supervisory, Waterflow 
UL 
 
 
ULC 
Y 
 
 
Y 
Alarm, Monitor, 
Supervisory, 
Waterflow 
 
Supervisory [6] 
Alarm 
 
 
Alarm 
 
[1]  Allowed only if the IDC is connected to the latching alarm device 
[2]  Allowed only when the supervising station supervises the telephone line and annunciates fault conditions 
within 200 seconds 
[3]  Prohibited when the control panel is connected to a supervising station 
[4]  The power supplies BPS6A, BPS6A/230, BPS10A, BPS10A/230 used for SIGA-REL are not compatible with 
FM sprinkler applications that require 90 hours of standby. 
[5]   CO alarm signals are required to activate TC4 CO evacuation signals but CO Supervisory or CO Monitor 
signals are not allowed to activate CO evacuation signals. CO alarm/CO supervisory/CO monitor signals shall not 
activate TC3 fire evacuation signals. 
[6]  CO detectors with a “CO alarm” device type must be programed using zones with bicolor LEDs (zones 13 
through 16 and 29 through 32) and the zone type must be set to Supervisory. The panel Event Notification must 
be set to Zone. Using this configuration ensures that when the “CO alarm” device type goes active, the panel 
displays a yellow LED indication instead of a red. This configuration complies with CAN/ULC-S527. 
[7]  UL 864 does not allow the use of alarm verified smoke detectors for activating releasing service applications.