Appendix B: Worksheets 
 
202  P/N 3102351-EN • REV 005 • ISS 28DEC18 
RZI16-2 24V IN riser maximum wire run calculation 
Use the APS/BPS notification appliance circuit calculation in the Remote Booster Power 
Supply Manual (P/N 3100485-EN) to calculate maximum wire run distance for RZI16-2 NAC 
circuits. 
RZI16-2 24V IN cable length 
  VS1 AUX1  VS4 AUX1  APS/BPS   
-2 alarm current   
0.85 
0.85  1 
A 
  ×  0.20  0.24  0.59   
Alarm current voltage drop
  = 
0.17 
0.20  0.59 
V 
    20.40  20.40  19.10  V 
  − 
0.17 
0.20  0.59 
V 
Minimum source output voltage
  = 
20.23 
20.20  18.51 
V 
-2 minimum input voltage  −  18.40  18.40  18.40  V 
  = 
1.83 
1.80  0.11 
V 
  ÷  0.85  0.85  1  A 
  =  2.15  2.21  0.11  Ω 
Wire resistance (Ω/ft) [2]
  ÷ 
0.00198 
0.00198  0.00198 
 
Maximum single wire length
  =  1, 087  1, 142  55  ft. 
÷ 
2 
2  2 
 
-wire cable 
 
= 
543 
535  27.5 
ft. 
[1] This voltage drop is valid for regulated notification appliances only.  
[2] For example, the value shown is typical resistance for 12 AWG 7-strand wire. Use the manufacturer’s 
published wire resistance expressed in ohms per foot. For other typical values, see Table 46 on page 197. 
[3] The value shown is for the VS4 panel. Maximum RZI16-2 24V IN riser cable distance length shown is based 
on using 12 AWG, 7-strand conductor cable.