Chapter 2: Front panel programming 
P/N 3102351-EN • REV 005 • ISS 28DEC18  91 
Device programming 
Each device that operates on a notification appliance circuit (NAC) or device loop has 
operating parameters that must be set. This includes assigning a device type and label, 
programming event notification, etc. 
Note: Addressable devices are programmed by entering the address of the device to be 
programmed, then setting the device options. It is important to have a printout of the Device 
Details > Serial Number report to correlate the device address with the default label and serial 
number. This will make device programming much easier. See “Device Details report” on page 
169. 
Table 26: Programming devices — Device options 
  Description 
  Identifies the zone to which the device will be added. 
To add the device to a zone, enter the zone number. 
— or — 
If the device will not be added to a zone, select Off. 
Note: Do not mix device and zone types. For example, do not place a nonlatching 
supervisory device in an alarm zone. When the supervisory device activates and an alarm 
event is initiated, the alarm event automatically clears when the device restores without 
having to reset the panel. 
  Identifies the zone to which the device’s secondary element (if it exists) will be added. 
To add the device to a zone, enter the zone number. 
— or — 
If the device will not be added to a zone, select Off. 
Note: Do not mix device and zone types. For example, do not place a nonlatching 
supervisory device in an alarm zone. When the supervisory device activates and an alarm 
event is initiated, the alarm event automatically clears when the device restores without 
having to reset the panel. Be sure to name your zones appropriately in message line 1 for 
CO activations. 
  Contains the two lines of text displayed beneath the device number on the LCD. 
1.  Enter text for the device label (two lines of 20 characters). 
2.  When you have finished, choose Save.