EasyManua.ls Logo

Kimo CPE 300 - F - Setpoinst and Time-Delay Setting

Kimo CPE 300
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.f - Setpoints and time-delay setting
7. Alarm / relay settings
Go into configuration mode (see page 5). The folder number displayed
corresponds to the last configuration folder used.
Select the folder “400” and validate with .
With and keys, select the setpoint value and validate with .
Note : the left column can be either a integer (from 0 to 9) or a negative sign
for a negative setpoint.
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 400.
7.f.1 - Setpoints
!
You must enter values according to the units of measurement selected, not
according to the measuring range of the transmitter.
Ex. on a CP 303 pressure transmitter (0 to ±1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must be
configured on measuring range of 0 to ±102 mmH2O. See conversion chart on page 11.
If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigure
the setpoints according to this new unit of measurement.
“403” “407” “411” “415”
Alarm 1 Alarm 2 Relay 1 Relay 2
To configure the setpoint 1, select sub-folder
and validate with .
d
b
u
o
s
M
806
d
b
u
o
s
M
814
d
b
u
o
s
M
822
d
b
u
o
s
M
830
“404” “408” “412” “416”
Alarm 1 Alarm 2 Relay 1 Relay 2
To configure the setpoint 2
b-folder
(alarm in control mode, see p17),
select su
and validate with .
d
b
u
o
s
M
808
d
b
u
o
s
M
816
d
b
u
o
s
M
824
d
b
u
o
s
M
832
1
Step
2
Step
3
Step
4
Step
Page 17
CPE 300 transmitter configuration via remote control / Modbus

Related product manuals