3. Maximum temperature maxTemp
The temperature moving average maximum value. The moving window depth is fixed at
1 minute.
The above described recorded values can be cleared, each group separately – when clearing a value,
all other values in the same groups are cleared too. Clearing values is explained in the Editing chapter
further down the manual.
Table 1.2: List of Measurement Quantities – COS Branch
abbreviation
symbol quantity unit
Pac
PAC
PACPAC
PAC
Instantaneous fundamental harmonic active power (Power
active).
kW / MW *
Pre
Pre
PrePre
Pre
Instantaneous fundamental harmonic reactive power (Power
reactive).
kvar / Mvar *
dPre
dPre
dPredPre
dPre
Instantaneous fundamental harmonic reactive power difference
to achieve target power factor (Delta Power reactive).
kvar / Mvar *
Temp
O
OO
O
C
CC
Cor
O
OO
O
F
FF
F
Instantaneous temperature (in the distribution board cabinet, at
the controller). Displayed in degrees Celsius or Fahrenheit, as
specified in parameter 58.
°C or °F
Acos
ACOS
ACOSACOS
ACOS
Average power factor in the power system over the time
specified in parameter 56 (Average cos).
—
mincos
nCOS
nCOSnCOS
nCOS
Minimum power factor in the power system achieved since last
clear. The evaluation window is specified in parameter 57.
—
APac
APAC
APACAPAC
APAC
Average fundamental harmonic active power in the power
system over the time specified in parameter 56 (Average
Power active).
kW / MW *
maxPac
m
mm
mPAC
PACPAC
PAC
Maximum fundamental harmonic active power in the power
system achieved since last clear. The evaluation window is
specified in parameter 57 (Maximum Power active).
kW / MW *
APre
APre
APreAPre
APre
Average fundamental harmonic reactive power in the power
system over the time specified in parameter 56 (Average
Power active).
kvar / Mvar *
maxPre
mPre
mPremPre
mPre
Maximum fundamental harmonic reactive power in the power
system achieved since last clear. The evaluation window is
specified in parameter 57 (Maximum Power reactive).
kvar / Mvar *
maxdPre
mdPr
mdPrmdPr
mdPr
Maximum fundamental harmonic reactive power difference to
achieve target power factor in the power system achieved
since last clear. The evaluation window is specified in
parameter 57 (Maximum Delta Power reactive).
kvar / Mvar *
maxTemp
m
mm
m
O
OO
O
C
CC
C or
M
MM
M
O
OO
O
F
FF
F
Maximum temperature recorded since last clear. The
evaluation is based on temperature one-minute moving
averages (Maximum Temperature).
°C or °F
* … in kW-, kvar- units as default; flashing decimal point indicates value in MW, Mvar
1.9.1.2.2 A Branch
All quantities related to current are shown in this branch. The maxTHDI value can be cleared
manually.