Novar 1xxx KMB systems
61
Tab. 6.2 : List of the Novar-1414 Measurement Quantities – Cos Branch
abbreviation
symbol quantity unit
cos1
cosI
cosIcosI
cosI
Instantaneous power factor of phase L1 -
cos2
cos2
cos2cos2
cos2
Instantaneous power factor of phase L2 -
cos3
cos3
cos3cos3
cos3
Instantaneous power factor of phase L3 -
Pac
PAC
PACPAC
PAC
Instantaneous fundamental harmonic active power (Power
active).
kW / MW *
… …
… etc.
6.2.3 A Branch
All quantities related to current are shown in this branch. Despite of standard models , quantities Iact,
Irea , dIrea and maxTHDI are removed.
Tab. 6.3 : List of the Novar-1414 Measurement Quantities – A Branch
abbreviation
symbol quantity unit
I1eff
iI
iIiI
iI
Instantaneous current effective value of phase L1 A / kA *
I2eff
i2
i2i2
i2
Instantaneous current effective value of phase L2 A / kA *
I3eff
i3
i3i3
i3
Instantaneous current effective value of phase L3 A / kA *
THDI1
tHdI
tHdItHdI
tHdI
Instantaneous level of total harmonic distortion of L1-phase
current
%
THDI2
tHd2
tHd2tHd2
tHd2
Instantaneous level of total harmonic distortion of L2-phase
current
%
THDI3
tH
tHtH
tHd3
d3d3
d3
Instantaneous level of total harmonic distortion of L3-phase
current
%
3. ÷ 19.har
of
currents
I1, I2, I3
3HI
3HI3HI
3HI/ 2
2 2
2 / 3
33
3
÷
!9HI
!9HI !9HI
!9HI/ 2
2 2
2 / 3
33
3
Instantaneous level of 3÷19-th harmonic component of
L1/L2/L3-phase current
%
* … in A as default; flashing decimal point indicates value in kA
6.2.4 V Branch
Displayed quantities are equal to standard controller models ones.
6.3 Installation
6.3.1 Measurement Currents
It is recommended metering current transformer (CT) outputs to be connected as follows :
• L1- phase current to terminals 41 ( k ) and 42 ( l )
• L2- phase current to terminals 43 ( k ) and 44 ( l )
• L3- phase current to terminals 1 ( k ) and 2 ( l )
A metering current transformer of nominal output current 5 or 1 A can be used.